LOW VOLTAGE
(380V-1140V) (CCC certification)
LHCKJ50-(125~160)A/1140V
CKJ5-80A~160A/1140V
CKJ5-400A/1140V
CKJ5-250A/1140V
CKJ313-630A/1140V
CKJ3-(800,1000,1250)A/1140V
CKJ7-1600A/1140V
CKJ2-(800,1000,1250)A/1140V
MEDIUM VOLTAGE(2000V-3600V) (2000v,for rotor
circuit use)
CKJ3-800/1000/1250-2KV
CKJ2-800/1000/1250-2KV
CKJ7-1600A/2KV
CKJ1-1600A/2KV
JCZ3-3.6-200/400
JCZ9-3.6/D400-4T
HIGH VOLTAGE(6000V-12000V)
JCZ5-7.2-160/250/400/630
JCZ5-12-160/250/400/630
JCZ7-7.2-160/250/400/630
JCZ7-12-160/250/400/630
JCZ1-7.2-160/250/400/630
JCZ1-12-160/250/400/630
JCZ7-12-160/250/400/630
JCZ8-7.2/12-160/250/400/630
SUPERVOLTAGE(24000V-35000V)
JCZ1-40.5/D630
FC WITHDRAWABLE VACUUM CONTACTOR 7.2kV
LHJCZR2-7.2JY/D315-40TM
LHJCZR2-7.2JY/D315-40TM
LHJCZR2-7.2JY/D315-40TM
LHJCZR2-7.2JY/D315-40TM
12kV LHJCZR2-12JY/D200-40TM
LHJCZR2-12JY/D200-40TM
LHJCZR2-12JY/D200-40TM
LHJCZR2-12JY/D200-40TM
Rất mong được hợp tác cùng quý công ty!
Qúy khách vui lòng liên hệ để được chăm sóc và có giá tốt nhất:
Mr.Hoàng Thiệu : 0904.756.286_0985.511.828
Email : hoangthieu0101@gmail.com
Yahoo : thieujs
Skype : Hoangthieu0101
EVS vacuum contactor
EVS-160 vacuum contactor
EVS-250 vacuum contactor
EVS-400 vacuum contactor
EVS-630 vacuum contactor
EVS-160A vacuum contactor
EVS-250A vacuum contactor
EVS-400A vacuum contactor
EVS-630A vacuum contactor
The vacuum is exchanged the contactor serial CKJ5-63A
The vacuum is exchanged the contactor serial CKJ5-80A
The vacuum is exchanged the contactor serial CKJ5-125A
The vacuum is exchanged the contactor serial CKJ5-160A
The vacuum is exchanged the contactor serial CKJ5-250A
The vacuum is exchanged the contactor serial CKJ5-400A
The vacuum is exchanged the contactor serial CKJ5-600A
CKG3-160
CKG3-630
CKG3-400
CKG3-250
CKG3-160A
CKG3-630A
CKG3-400A
CKG3-250A
CKG3-160A/6KV
CKG3-630A/6KV
CKG3-400A/6KV
CKG3-250A/6KV
CKG3-160/6KV
CKG3-630/6KV
CKG3-400/6KV
CKG3-250/6KV
CKG3-160A/6
CKG3-630A/6
CKG3-400A/6
CKG3-250A/6
CKG3-160/6
CKG3-630/6
CKG3-400/6
CKG3-250/6
CKG3-160/7.2
CKG3-630/7.2
CKG4-160/12KV vacuum contactor ccc
CKG4-630/12KV vacuum contactor ccc
CKG4-400/12KV vacuum contactor ccc
CKG4-250A/12KV vacuum contactor ccc
CKG4-160A/12KV vacuum contactor ccc
CKG4-630A/12KV vacuum contactor ccc
CKG4-400A/12KV vacuum contactor ccc
CKG4-250A/12KV vacuum contactor ccc
(SINGLE-POLE) TYPE AC L.V. VACUUM CONTACTOR
General description
CKJP-125, 259, 400, 600/1.14 (single-pole) type AC vacuum contactor is applicable to electrical system with AC 50Hz, primary feedback circuit rated operating rated voltage 600-1140V, rated operating current 125-600A current, closing and breaking circuit and starting and controlling AC motor frequently, it is also applicable to magnetic force starter of different range of protecting, in particular, suitable for composing explosion proof magnetic starter.
2. CKJ11-125,160 (VERTICAL YYPE)
3. CKJ11-125A/1.14KV(HORIZONTAL TYPE)
TYPE AC L.V. BACUUM CONTACTOR
CKJ11-125, 160 type vacuum contactor can be into vertical and horizontal contactors two types both of which use ZKTJ 125/1.14 type vacuum switch tube as arc extinguisher. The main contact is closed in the vacuum switch tube, so arc can’t be bared. The product has the features of reliability, strong differentiate capacity, long endurance, and small cubage. It is suitable for the electric system with AC 50Hz, rated operating voltage of 1140V, and rated operating current of 160A for opening and closing the main circuit directing or at far. This product especially suits for explosion-proof electromagnetic starter in the mine for controlling continually operating tri-phase induction-motor, also for closing and open other over load.
Main technical parameter
Type
|
Rated voltage (V)
|
Rated current (A)
|
Main contact parameter
| |||
Main circuit
|
Control circuit
|
Clearance between open contacts(mm)
|
Over travel
(mm)
|
Final pressure
(N)
| ||
CKJ□-
160
|
1140
|
36, 220, 380
|
125
160
|
1±0.2
|
30±3
|
Type
|
Making capacity
|
Breaking capacity
|
Limit breaking current(A)
|
Electricity life times AC-4
|
Mechanical life times
|
weight
|
125
CKJ□-
160
|
10le, 100times
|
8le, 25times
|
2000, 3times
|
3.7kg
|
Outline and installation dimensions
4. CKJ5-63, 80, 125, 250, 400, 600
AC L.V VACUUM CONTACTOR
Main technical parameter
Rated voltage (V)
|
Rated current
(Main circuit) A
|
Main contact parameter
|
Power frequency voltage resistance (effective value)
| ||||||
Main circuit
|
Control circuit
|
Opening distance (mm)
|
Over travel (mm)
|
Final pressure (N)
|
Main circuit
|
Auxiliary circuit
|
Control circuit
| ||
1140
|
36.110.220.380
|
80
|
1.8±0.2
|
1±0.2
|
30±3
|
4200
|
2500
|
2000
| |
CKJ5-125
|
1140
|
36.110.220.380
|
125
|
1.8±0.2
|
1±0.2
|
30±3
|
4200
|
2500
|
2000
|
CKJ5-250
|
1140
|
36.110.220.380
|
250
|
2±0.2
|
1±0.2
|
78±7.8
|
4200
|
2500
|
2000
|
CKJ5-400
|
1140
|
36.110.220.380
|
400
|
2±0.2
|
1±0.2
|
117.6±11.8
|
4200
|
2500
|
2000
|
CKJ5-600
|
1140
|
36.110.220.380
|
600
|
2±0.2
|
1±0.2
|
196±19.6
|
4200
|
2500
|
2000
|
Product model
|
Making capacity
|
Breaking capacity
|
Limit breaking current(A)
|
Electricity life time
|
Mechanic life time
|
Weight
| |
AC-3
|
AC-4
| ||||||
CKJ5-80
|
10le, 100 times
|
8le, 25 times
|
2000, 3 times
|
6×104
|
300×104
|
4kg
| |
CKJ5-125
|
10le, 100 times
|
8le, 25 times
|
2000, 3 times
|
6×104
|
6×104
|
300×104
|
4kg
|
CKJ5-250
|
10le, 100 times
|
8le, 25 times
|
4500, 3 times
|
6×104
|
6×104
|
300×104
|
8kg
|
CKJ5-400
|
10le, 100 times
|
8le, 25 times
|
4500, 3 times
|
6×104
|
2×104
|
300×104
|
12kg
|
CKJ5-600
|
10le, 100 times
|
8le, 25 times
|
6000, 3 times
|
6×104
|
0.5×104
|
300×104
|
20kg
|
5. CKJ20-800A, CKJ5-1000A (VERTICAL TYPE) AC CONTACTOR
Main technical parameter
Type
|
CKJ20-630/1140
|
CKJ20-800/1140
|
Rated main loop voltage(V)
|
1140
|
1140
|
Rated main loop current(A)
|
630
|
800
|
Mechanical life(ten-thousand times)
|
300
|
300
|
Clearance between open contactors (mm)
|
2.5±0.3
|
2.5±0.3
|
Over travel (mm)
|
≧1
|
≧1
|
Outline and installation dimensions
6. CZG1-7.2/160A
7. ZN-7.2/600
TYPE AC H.V. VACUUM CONTACTOR
Outline and installation dimensions
8. ZKJ-350/3.3
MINING AC H.V. VACUUM CONTACTOR
CKJ-200/3
TYOE AC H.V. VACUUM CONTACTOR
Main technical parameter
Rated voltage (V)
|
Rated current
(Main circuit) A
|
Main contact parameter
|
Power frequency voltage resistance (effective value)
| ||||||
Main circuit
|
Control circuit
|
Opening distance (mm)
|
Over travel (mm)
|
Final pressure (N)
|
Main circuit
|
Auxiliary circuit
|
Control circuit
| ||
ZKJ-350/3.3
|
3000
|
110, 220
|
200
|
3.5±0.3
|
1.5±0.3
|
100±20
|
23000
|
2500
|
2000
|
CKJ-200/3
|
3000
|
110, 220
|
200
|
3.5±0.3
|
1.5±0.3
|
100±20
|
23000
|
2500
|
2000
|
Product model
|
Making capacity
|
Breaking capacity
|
Limit breaking current (A)
|
Overloading capability
|
Mechanic life time
|
weight
|
AC-4
|
10le, 100time
|
8le, 25time
|
4500, 3 time
|
8le, 10s
|
300×104
|
21kg
|
9. CKG3-7.2/160, 250, 400, 630
TYPE AC H.V. VACUUM CONTACTOR
Main technical parameter
Product model
|
Rated voltage (V)
|
Rated current
(Main circuit) A
|
Main contact parameter
|
Power frequency voltage resistance (effective value)
| ||||||||
Main circuit
|
Control circuit
|
Opening distance (mm)
|
Over travel (mm)
|
Final pressure (N)
|
Main circuit
|
Auxiliary circuit
|
Control circuit
| |||||
7200
|
220/110
|
160
|
3.5±0.3
|
2±0.2
|
>85N
|
32000
|
2500
|
2000
| ||||
CKG3-7.2/250
|
7200
|
220/110
|
250
|
3.5±0.3
|
2±0.2
|
>85N
|
32000
|
2500
|
2000
| |||
CKG3-7.2/400
|
7200
|
220/110
|
400
|
3.5±0.3
|
2±0.2
|
>85N
|
32000
|
2500
|
2000
| |||
CKG3-7.2/630
|
7200
|
220/110
|
630
|
3.5±0.3
|
2±0.2
|
>85N
|
32000
|
2500
|
2000
| |||
Making capacity
|
Breaking capacity
|
Limit breaking current (A)
|
Overloading capability
|
Mechanic life time
|
weight
| |
CKG3-7.2/160
|
10le, 100time
|
8le, 25time
|
4
|
8le, 10s
|
100×104
|
25.5kg
|
CKG3-7.2/250
|
10le, 100time
|
8le, 25time
|
4
|
8le, 10s
|
25.5kg
| |
CKG3-7.2/400
|
10le, 100time
|
8le, 25time
|
4.5
|
8le, 10s
|
100×104
|
25.5kg
|
CKG3-7.2/630
|
10le, 100time
|
8le, 25time
|
5
|
8le, 10s
|
100×104
|
36kg
|
Outline and installation dimensions
10. CKG, KJ3-12/160, 250,400, 630
TYPE AC H.V. VACUUM CONTACTOR
Main technical parameter
Product model
|
Rated voltage (V)
|
Rated current
(Main circuit) A
|
Main contact parameter
|
Power frequency voltage resistance (effective value)
| ||||||||
Main circuit
|
Control circuit
|
Opening distance (mm)
|
Over travel (mm)
|
Final pressure (N)
|
Main circuit
|
Auxiliary circuit
|
Control circuit
| |||||
12000
|
220/110/380
|
160
|
5±0.5
|
2±0.2
|
>85N
|
42000
|
2500
|
2000
| ||||
CKG3-12/250
|
12000
|
220/110/380
|
160
|
5±0.5
|
2±0.2
|
>85N
|
42000
|
2500
|
2000
| |||
CKG3-12/400
|
12000
|
220/110/380
|
160
|
5±0.5
|
2±0.2
|
>85N
|
42000
|
2500
|
2000
| |||
CKG3-12/630
|
12000
|
220/110/380
|
160
|
5±0.5
|
2±0.2
|
>85N
|
42000
|
2500
|
2000
| |||
Product model
|
Making capacity
|
Breaking capacity
|
Limit breaking current (A)
|
Mechanic life time
|
weight
|
CKG3-12/160
|
10le, 100time
|
8le, 25time
|
100×104
|
25.5kg
| |
CKG3-12/250
|
10le, 100time
|
8le, 25time
|
10le
|
100×104
|
25.5kg
|
CKG3-12/400
|
10le, 100time
|
8le, 25time
|
10le
|
100×104
|
25.5kg
|
CKG3-12/630
|
10le, 100time
|
8le, 25time
|
10le
|
100×104
|
36kg
|
11. CKG3-12
SERIES SINGLE-POLE PERMANENT-MAGNET WACUUM CONTACTOR
12. CKG3-12KV-Y
SERIES PERMANCENT-MAGNET H.V. VACUUM CONTACTOR
General description
This series contactors are composed of insulation frame, metal base, transmission shaft and crutch, electromagnetic system, permanent-magnet, power module, auxiliary switch and vacuum interrupter and so on components. While electromagnetic coil across the control voltage, armature drives the crutch rotation to open the main contact in the vacuum interrupter. Meanwhile, auxiliary switch breaks power of electromagnetic coil, turns to be permanent-magnet maintenance. After power broke by control loop, energy storage power of power module discharges to electromagnetic coil for degaussing, and the main contact broke under the function of opening spring.
Outline and installation dimensions
13. JCZ5-12/250, 400, 630
TYPE AC H.V. VACUUM CONTACTOR
Main technical parameter
No.
|
Item
|
Unit
|
Data
| ||||||
JCZ5-7.2 J/D/630/400/250
|
JCZ5-122 J/D/630/400/250
| ||||||||
1
|
Rated voltage
|
KV
|
7.2
|
12
| |||||
2
|
Rated current
|
A
|
630
|
400
|
250
|
630
|
400
|
250
| |
Rated making current(effective value)
|
6300
|
4000
|
2500
|
6300
|
4000
|
2500
| |||
4
|
Rated max breaking current
|
5040
|
3200
|
2000
|
5040
|
3200
|
2000
| ||
5
|
4S thermal stability current
|
6300
|
4000
|
2500
|
6300
|
4000
|
2500
| ||
6
|
Limit breaking current
|
6300
|
4000
|
2500
|
6300
|
4000
|
2500
| ||
7
|
Power frequency with stand voltage
|
KV
|
32
|
42
| |||||
8
|
Permissible operation frequency
|
300
| |||||||
9
|
Electricity life
|
AC-3
|
×104
times
|
25
| |||||
AC-4
|
10
| ||||||||
10
|
Mechanical life
|
30
| |||||||
11
|
Rated operation voltage
|
v
|
AC 110/220
| ||||||
12
|
Closing coil operation current
|
A
|
≤DC6/3
| ||||||
13
|
Retaining coil retaining current
|
D:DC 0.32/0.16
| |||||||
14
|
Shunt coil release current
|
J:D 2.5/1.3
|
Outline and dimension
Không có nhận xét nào: